• Good Wholesale Vendors  Wired Rain Sensor - PH Sensor – Huacheng

Good Wholesale Vendors Wired Rain Sensor - PH Sensor – Huacheng

Short Description:


Product Detail

Product Tags

Related Video

Feedback (2)

With responsible good quality method, good status and excellent client services, the series of solutions produced by our company are exported to lots of countries and regions for Beaker Tri Corner, Disposable Pipett, Portable Multi Parameter Water Analysis Kit, We have confident that we can provide the high quality products at resonable price, good after-sales service to the customers. And we will create a bright future.
Good Wholesale Vendors Wired Rain Sensor - PH Sensor – Huacheng Detail:

The new-generation PHTRSJ soil pH sensor solves the shortcomings of traditional soil pH that requires professional display instruments, tedious calibration, difficult integration, high power consumption, high price, and difficult to carry.

● New soil pH sensor, realizing online real-time monitoring of soil pH.
● It adopts the most advanced solid dielectric and large-area polytetrafluoroethylene liquid junction, which is not easy to block and maintenance-free.
● High integration, small size, low power consumption, easy to carry.
● Realize low cost, low price and high performance.
● High integration, long life, convenience and high reliability.
● Simple operation.
● Support secondary development.
● The electrode uses high-quality low-noise cable, which can make the signal output length up to 20 meters without interference.

This product can be widely used in the fields of agricultural irrigation, flower gardening, grassland pasture, rapid soil testing, plant cultivation, scientific experiments and so on.

Measuring range 0-14pH
Accuracy ± 0.1pH
Resolution 0.01pH
Response time <10 seconds (in water)
Power supply mode DC 12V 
DC 24V 
Other
Output form Voltage: 0~5V 
Current: 4 ~ 20mA
RS232
RS485
Other
Instrument Line length Standard: 5 meters
Other  
Working environment Temperature 0 ~ 80 ℃
Humidity: 0 ~ 95% RH
Power consumption 0.2W
Housing material waterproof plastic shell
Transmitter size 98 * 66 * 49mm

Voltage type (0 ~ 5V output):
D = V / 5 × 14
(D is the measured pH value, 0.00pH≤D≤14.00pH, V is the output voltage (V))

Current type (4 ~ 20mA output):
D = (I-4) / 16 × 14
(D is the measured pH value, 0.00pH≤D≤14.00pH, I is the output current (mA))

(1) If equipped with a weather station produced by our company, directly connect the sensor to the corresponding interface on the weather station using a sensor line.
(2) If the transmitter is purchased separately, the cable sequence of the transmitter is:

Line color

Output signal

Voltage type

Current type

Communication

type

Red

Power +

Power +

Power +

Black (green)

Power ground

Power ground

Power ground

Yellow

Voltage signal

Current signal

A+/TX

Blue

 

 

B-/RX

PH Sensor1

1. The serial format
Data bits 8 bits
Stop bit 1 or 2
Check Digit None
Baud rate 9600 Communication interval is at least 1000ms
2. Communication format
[1] Write device address
Send: 00 10 Adress CRC (5 bytes)
Returns: 00 10 CRC (4 bytes)
Note: 1. The address bit of the read and write address command must be 00.
2. Adress is 1 byte and the range is 0-255.
Example: Send 00 10 01 BD C0
Returns 00 10 00 7C
[2] Read device address
Send: 00 20 CRC (4 bytes)
Returns: 00 20 Adress CRC (5 bytes)
Explanation: Adress is 1 byte, the range is 0-255
For example: Send 00 20 00 68
Returns 00 20 01 A9 C0
[3] Read real-time data
Send: Adress 03 00 00 00 01 XX XX
Note: as shown below:

Code

Function definition

Note

Adress

Station number (address)

 

03

Function code

 

00  00

Initial address

 

00  01

Read points

 

XX XX

CRC Check code, front low later high

 

Returns: Adress 03 02 XX XX XX XX

Code

Function definition

Note

Adress

Station number (address)

 

03

Function code

 

02

Read unit byte

 

XX  XX

Data (high before, low after)

Hex

XX  XX

CRCCheck code

 

To calculate the CRC code:
1. The preset 16-bit register is FFFF in hexadecimal (that is, all are 1). Call this register the CRC register.
2. XOR the first 8-bit data with the lower bit of the 16-bit CRC register and put the result in the CRC register.
3. Shift the contents of the register to the right by one bit (toward the low bit), fill the highest bit with 0, and check the lowest bit.
4. If the least significant bit is 0: repeat step 3 (shift again), if the least significant bit is 1: the CRC register is XORed with the polynomial A001 (1010 0000 0000 0001).
5. Repeat steps 3 and 4 until 8 times to the right, so that the entire 8-bit data has been processed.
6. Repeat steps 2 to 5 for the next 8-bit data processing.
7. The CRC register finally obtained is the CRC code.
8. When the CRC result is put into the information frame, the high and low bits are exchanged, and the low bit is first.

PH Sensor2

1. When the sensor leaves the factory, the probe is provided with a transparent protective cover, and the built-in protective liquid protects the probe. When using, please remove the protective cover, fix the filter tank and the sensor, and then use the attached cable tie to wrap the filter in the filter tank. To prevent direct contact between the soil and the probe and damage the probe. In actual use, please ensure that the filter trough and the filter are firmly connected. Do not remove the filter trough and the filter. Insert the probe directly into the soil to avoid making the probe damage and unrepairable.
2. Insert the probe part vertically into the soil. The depth of the probe must be at least covered by the filter. Under normal circumstances, the pH in the air is between 6.2 and 7.8.
3. After burying the sensor, pour a certain amount of water around the soil to be measured, wait for a few minutes, and wait for the water to soak into the probe, then you can read the data on the instrument. Under normal circumstances, the soil is neutral and the pH is between Around 7, the actual pH value of the soil in different places will be different, it should be determined according to the actual situation.
4. The user can use the attached 3 pH reagents and configure according to the configuration method to check whether the product performance is normal.

1. In the pipeline in order to ensure the correct electrode measured pH value should be avoided during the measurement of air bubbles caused by inaccurate data;
2. Please check whether the packaging is intact and check whether the product model is consistent with the selection;
3. Do not connect with power on, and then power on after checking the wiring.
4. Do not arbitrarily change the components or wires that have been soldered when the product leaves the factory.
5. The sensor is a precision device. Please do not disassemble it by yourself or touch the surface of the sensor with sharp objects or corrosive liquids during use to avoid damaging the product.
6. Please keep the verification certificate and certificate of conformity, and return it with the product when repairing.

1. For analog output, the display indicates that the value is 0 or is out of range. The collector may not be able to obtain the information correctly due to wiring problems. Please check whether the wiring is correct and firm, and the power voltage is normal;
2. If it is not the above reasons, please contact the manufacturer.

1. The input end of the instrument (measuring electrode socket) must be kept dry and clean to prevent dust and water vapor from entering.
2. Avoid long-term immersion of electrodes in protein solution and acid fluoride solution, and avoid contact with silicone oil.
3. After long-term use of the electrode, if the slope is slightly reduced, the lower end of the electrode can be immersed in a 4% HF solution (hydrofluoric acid) for 3 to 5 seconds, then washed with distilled water and then immersed in 0.1mol / L hydrochloric acid Refresh the electrode.
4. In order to make the measurement more accurate, the electrode must be calibrated frequently and washed with distilled water.
5. The transmitter should be placed in a dry environment or a control box to avoid meter leakage or measurement error caused by water droplets splashing or being wet.


Product detail pictures:

Good Wholesale Vendors  Wired Rain Sensor - PH Sensor – Huacheng detail pictures


Related Product Guide:

We will devote ourselves to giving our esteemed buyers using the most enthusiastically thoughtful services for Good Wholesale Vendors Wired Rain Sensor - PH Sensor – Huacheng , The product will supply to all over the world, such as: Netherlands, belarus, USA, Each product is carefully made, it will make you satisfied. Our products in the production process have got strictly monitored, because it is only to provide you the best quality, we will feel confident. High production costs but low prices for our long-term cooperation. You can have a variety choices and the value of all types are same reliable. If you have any question, do not hesitate to ask us.
  • This company has a lot of ready-made options to choose and also could custom new program according to our demand, which is very nice to meet our needs.
    5 Stars By Adelaide from Saudi Arabia - 2017.08.28 16:02
    Timely delivery, strict implementation of the contract provisions of the goods, encountered special circumstances, but also actively cooperate, a trustworthy company!
    5 Stars By olivier musset from Uganda - 2018.12.05 13:53
    Write your message here and send it to us

    Related products

    • Special Price for Disposable Pipett - CLEAN MD110 Ultra-thin Digital Magnetic Stirrer – Huacheng

      Special Price for Disposable Pipett - CLEAN MD...

      ●60-2000 rpm (500ml H2O) ●LCD screen displays working and setting status ●11mm ultra-thin body, stable and space-saving ●Quiet, no loss, no maintenance ●Clockwise and counterclockwise (automatic) switching ●Off timer setting ●Compliant with CE specifications and does not interfere with electrochemical measurements ●Use environment 0-50°C Rated Voltage 100 – 240VC Rated frequency 50-6Hz Output voltage 12VDC Input power 5W Magnetic Stirrer Quadrupole Drive Coil Display LCD ...

    • OEM/ODM Factory Hot Sale And Popular Univeral Pipette - Microcomputer automatic calorimeter – Huacheng

      OEM/ODM Factory Hot Sale And Popular Univeral P...

      Microcomputer automatic calorimeter is suitable for electric power, coal, metallurgy, petrochemical, environmental protection, cement, papermaking, ground can, scientific research institutions and other industrial sectors to measure the calorific value of coal, coke and petroleum and other combustible materials. In line with GB/T213-2008 “Coal thermal determination Method” GB/T384 “Determination of calorific value of petroleum products” JC/T1005-2006 “Cement blac...

    • Manufacturer for O3 Gas Alarm - Portable pump suction single gas detector User’s Manual – Huacheng

      Manufacturer for O3 Gas Alarm - Portable pump ...

      System configuration 1. Table1 Material List of Portable pump suction single gas detector Gas Detector USB Charger Please check materials immediately after unpacking. The Standard is necessary accessories. The Optional can be chosen according to your needs. If you have no need to calibrate, set the alarm parameters, or read the alarm record, don’t purchase the optional accessories. System parameter Charging Time: about 3hours~6 hours Charging Voltage: DC5V Service Time: Combustible ...

    • Manufactur standard Ac Evaporator Temperature Sensor - PH Sensor – Huacheng

      Manufactur standard Ac Evaporator Temperature S...

      The new-generation PHTRSJ soil pH sensor solves the shortcomings of traditional soil pH that requires professional display instruments, tedious calibration, difficult integration, high power consumption, high price, and difficult to carry. ● New soil pH sensor, realizing online real-time monitoring of soil pH. ● It adopts the most advanced solid dielectric and large-area polytetrafluoroethylene liquid junction, which is not easy to block and maintenance-free. ● High integration, small size, l...

    • Popular Design for Ultrasonic Open Channel Flow Meter - CLEAN MD110 Ultra-thin Digital Magnetic Stirrer – Huacheng

      Popular Design for Ultrasonic Open Channel Flow...

      ●60-2000 rpm (500ml H2O) ●LCD screen displays working and setting status ●11mm ultra-thin body, stable and space-saving ●Quiet, no loss, no maintenance ●Clockwise and counterclockwise (automatic) switching ●Off timer setting ●Compliant with CE specifications and does not interfere with electrochemical measurements ●Use environment 0-50°C Rated Voltage 100 – 240VC Rated frequency 50-6Hz Output voltage 12VDC Input power 5W Magnetic Stirrer Quadrupole Drive Coil Display LCD ...

    • China wholesale Automatic Rain Detector - Ultrasonic Level Difference Meter – Huacheng

      China wholesale Automatic Rain Detector - Ultr...

      ● Stable and reliable: We choose high-quality modules from the power supply part in circuit design, and select high-stable and reliable devices for the procurement of key components; ● Patented technology: Ultrasonic intelligent technology software can perform intelligent echo analysis without any debugging and other special steps. This technology has the functions of dynamic thinking and dynamic analysis; ● High precision: The ultrasonic level gauge has high precision, and the liquefaction p...